Sealing Materials Plant
Manufacturer of materials and technologies Abris.
Section: Panels
TU: 23.99.19-021-52471462-2017
A combined panel consisting of a radiation-protective part (barite-filled material Abris RZ, lead plate) and construction and finishing material (glass-magnesium sheets, glass-cement panels, metal sheets, plasterboard sheets, etc.). The back side of the panel is covered with a protective film. The thickness and design of the radiation protection part is formed depending on the required lead equivalent.
Scope of application:
designed to protect building structures from ionizing radiation as a covering for walls and ceilings in medical, scientific and industrial premises. Also, the barite panel has vibration and noise-absorbing properties.
Along with radiation-protective properties, Abris barite panels effectively reduce the level of sound pressure. Airborne sound insulation index Rw - 59 dB with a panel thickness of 15 mm in accordance with GOST 27296.
Barite panel Abris | Lead equivalent of barite panel Outline, mm Pb (the anode voltage on the X-ray tube is 100 kV) | |||||
0,5 mm | 1,0 mm | 1,5 mm | 2,0 mm | 2,5 mm | 3,0 mm | |
Form | panel | panel | panel | panel | panel | panel |
Width, mm | 600 | 600 | 600 | 600 | 600 | 600 |
Length, mm | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 |
Thickness, mm | 10 | 15 | 11/1 | 16/1 | 13/2 | 17/2 |
Thickness of the glass-magnesium sheet , mm | 6 | 6 | 6 | 6 | 6 | 6 |
Thickness of lead sheet, mm | - | - | 1 | 1 | 2 | 2 |
Estimated panel weight, kg | 11,30±2 | 19,65±2 | 19,50±2 | 27,84±2 | 29,40±2 | 36,00±2 |
Abris barite panel has vibration, noise-absorbing properties.
Instructions for use
When applying, you should be guided by the project documentation approved in accordance with the established procedure.
Work on the installation and cladding of structures using barite panels Abris is carried out under dry and normal humidity conditions at a temperature not lower than +15 °C.
Installation should be carried out in accordance with the instructions for the use of barite panels Abris. Use a metal profile and brackets for drywall for the installation of radiation-protective barite panels Abris.
The parts can be attached in both transverse and longitudinal directions. System fasteners (screws) are used to attach the panels to the frame.
All joints and abutments are filled with self–adhesive radiation-protective material: Abris RZsk-01-LB tape or Abris RZsk-01-Sh cord.
Next, decorative finishing is carried out (painting, ceramic tile cladding, decorative plastering, etc.).